HEAD LOSSES
Example:
Burner TBG 1600LX ME
Power to obtain: 10.500 kW
Pressure in the combustion chamber: 6 mbar
On the leakage curve at the combustion head at the power of 10.500
kW, a leakage of 130 mbar is obtained.
Add the back pressure in chamber to these values: 130+6 = 136 mbar.
This is the pressure at the pressure tap to obtain a power of 10.500 kW.
Then proceed to adjust the valve and check the flow rate.
0
50
100
150
200
250
300
2500
3500
4500
5500
6500
7500
8500
9500
10500
11500
12500
13500
14500
15500
mbar / hPa
kW
1500
Perd_testa_67570010
18 / 28
0006160509_202301
ENGLISH