13 / 15
0006081370_200807
E
N
G
L
I
S
H
IMPORTANT The above adjustments are indicative only;
position the combustion head according
to the characteristics of the combustion
chamber
X= Distance between combustion head and disk; adjust the
distance X following the indications below:
a) slacken screw 1
b) turn screw 2 to position the combustion head 3, referring
to index 4.
c) adjust the distance X between minimum and maximum
according the indications in the table.
COMBUSTION HEAD ADJUSTMENT SCHEME
BURNER
X
Value indicated by
index 4
TBG 45ME
3 ÷31
0 ÷ 3,2
TBG 60ME
6÷ 34
0 ÷ 3,2
fig. 1
fig-2
MAINTENANCE
Carry out periodic analysis of the exhaust combustion gas,
checking the emissions.
Periodically replace the gas filter when dirty.
Check that all the components of the combustion head are
in a good state, not deformed by the temperature and free
from impurities or deposits from the installation environment
or by poor combustion and check also the electrodes are
working efficiently.
If the combustion head needs to be cleaned, remove the
components following the procedure indicated below:
1) Slacken the screws 1 and remove the lid 2 (figure 1).
2) Make sure that mobile plate 3 is held in place by screw 4. This
will permit the mixer unit to be reassembled in the position adju
-
sted previously after completion of maintenance work. Slacken
screw 5, which anchors the unit’s forward movement rod to the
mobile plate (figure 2).
3) Completely unscrew the nut (6) and tighten the screw (7), mo
-
ving it forward inside the gas delivery connection (8) far enough
to permit subsequent dismantling of the mixing unit. Slightly rai
-
se the gas delivery union (8) out of its housing (figure 3).
4) Completely remove the mixing unit, pulling it out in the direction
shown by arrow 9, after pulling the ignition and ionisation ca
-
bles 10 out of their electrodes (figure 4).
Complete maintenance operations, proceed with re-assem
-
bly of the combustion head, following the above instruc
-
tions in reverse order, after having checked the correct po
-
sition of the ignition and ionisation electrodes
(see diagram
0002935680).