TECHNICAL SPECIFICATIONS
MODEL
TBG 80 LX ME TBG 110 LX ME TBG 140 LX ME TBG 200 LX ME
Type-approval PIN
CE-0085BS0067 CE-0085BS0067 CE-0085BS0067 CE-0085BS0067
Maximum natural gas heat power
kW
800
1200
1450
1900
Minimum natural gas heat power
kW
130
180
200
475
¹) natural gas emissions
mg/kWh
Class 3
Class 3
Class 3
Class 3
Operation
Electronic
modulation
Electronic
modulation
Electronic
modulation
Electronic
modulation
50 Hz natural gas transformer
26 kV 40 mA -
230 V
26 kV 40 mA -
230 V
26 kV 40 mA -
230 V
26 kV 40 mA -
230 V
Methane maximum flow rate
Stm³/h
85
127
153
201
Methane minimum flow rate
Stm³/h
14
19
21
50
Maximum natural gas pressure
hPa (mbar)
360
360
360
360
Minimum natural gas pressure
hPa (mbar)
23
26
36
44
50hz fan motor
kW
1.1
1.5
2.2
3
50Hz three-phase electrical data
3L - 400V - 2.5A -
1.35kW
3L - 400V - 3.1A -
1.76kW
3L - 400V - 4.6A -
2.46kW
3L - 400V - 6.3A -
3.49kW
50Hz single-phase electrical data
1N - 230V - 0.44A -
0.101kW
1N - 230V - 0.44A -
0.101kW
1N - 230V - 0.44A -
0.101kW
1N - 230V - 0.44A -
0.101kW
Protection rating
IP40
IP40
IP40
IP40
Flame detection
IONISATION
PROBE
IONISATION
PROBE
IONISATION
PROBE
IONISATION
PROBE
Control box
BT 320
BT 320
BT 320
BT 320
Air flow rate regulation
ELECTRONIC
CAM
ELECTRONIC
CAM
ELECTRONIC
CAM
ELECTRONIC
CAM
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
75
77
83
85
Weight with packaging
kg
78
88
92
95
Weight without packaging
kg
57
67
71
74
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion chamber.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).
STANDARD ACCESSORIES
MODEL
TBG 80 LX ME
TBG 110 LX ME
TBG 140 LX ME
TBG 200 LX ME
Burner connection flange
2
2
2
2
Burner coupling flange gasket
1
1
1
1
Stud bolts
No. 4 M 12
No. 4 M 12
No. 4 M 12
No. 4 M 12
Hexagon nuts
No. 4 M 12
No. 4 M 12
No. 4 M 12
No. 4 M 12
Flat washers
No. 4 Ø 12
No. 4 Ø 12
No. 4 Ø 12
No. 4 Ø 12
6 / 34
0006081328_202202
ENGLISH
Summary of Contents for TBG 80 LX ME
Page 2: ......
Page 32: ...SCHEMI ELETTRICI TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ITALIANO...
Page 33: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ITALIANO...
Page 34: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ITALIANO...
Page 36: ...34 34 0006081328_202202 ITALIANO...
Page 66: ...WIRING DIAGRAMS TBG 80 360LX ME TBG 80 360 ME 30 34 0006081328_202202 ENGLISH...
Page 67: ...TBG 80 360LX ME TBG 80 360 ME 31 34 0006081328_202202 ENGLISH...
Page 68: ...TBG 80 360LX ME TBG 80 360 ME I1 I2 BA I4 I3 32 34 0006081328_202202 ENGLISH...
Page 70: ...34 34 0006081328_202202 ENGLISH...
Page 71: ......