9 / 26
0006081537_201311
ENGLISH
fig. 4
fig. 3
fig. 2
fig. 1
ELECTRICAL CONNECTIONS
The three-phase power supply line must have a switch with fuses.
Moreover, the Standards require a switch on the burner power supply
line, placed outside the boiler room and in an easily accessible position.
For the electrical connections (line and thermostats), follow the attached
wiring diagram. To carry out the connection of the burner to the power
supply line proceed as follows:
• Remove the lid by unscrewing the 4 screws (1) in figure 1, without
removing the transparent door. In this way the burner’s electrical
panel can be accessed.
• Loosen the screws (2) and, after removing the cable float plate (3),
pass the two 7 and 4-pole plugs through the hole (see figure 2).
• Reposition the cable float plate as in figure 3. Turn the cam (6) so
that the plate exerts sufficient pressure on the two cables, then
tighten the screws that fasten the plate. Finally connect the two 7
and 4-pole plugs.
the housings for the cables for the 7 and 4-pole plugs are
provided respectively for cable Φ 9.5÷10 mm and Φ 8.5÷9
mm, this ensures that the protection rating is iP 54 (standard
ieC en60529) for the electrical panel.
• To close the switchboard cover, tighten the 4 screws (1) to a torque
of approx. 5 Nm in order to ensure proper sealing. Now, to gain
access to the control panel (8), release the clear door (7), by slightly
prising with a tool (e.g. screwdriver) in the direction of the arrows
shown in figure 4, let it slide shortly and then separate it from cover.
• To secure the transparent door on the panel properly, proceed as
indicated in figure 5: position the hooks at their hooking points and
(9) slide the door in the direction indicated by the arrow until it clicks.
It is now well sealed.
important: only professionally qualified personnel may open
the burner electrical panel.
Before performing maintenance works disconnect the
power supply and make sure it cannot be re-connected
by accident. the inverter remains hot for a few minutes,
resulting in risk of skin burns or injuries.
the inverter can still be charged with high voltage, even
when disconnected from the mains power.
Before performing any installation work on the equipment, wait five
minutes after deactivating it.
fig. 5
Summary of Contents for TBG 80 LX PN V
Page 2: ......
Page 26: ...24 26 0006081537_201311 ENGLISH MINIMUM IONISATION CURRENT 3 μA OPTIONAL WIRING DIAGRAM ...
Page 28: ...26 26 0006081537_201311 ENGLISH ...
Page 54: ...26 26 0006081537_201311 ESPAÑOL ...
Page 80: ...26 26 0006081537_201311 FRANÇAIS ...
Page 104: ...24 26 0006081537_201311 TÜRKÇE ASGARİ İYONİZASYON AKIMI 3 µA TALEP ÜZERİNE ELEKTRİK ŞEMASI ...
Page 106: ...26 26 0006081537_201311 TÜRKÇE ...
Page 132: ...26 26 0006081537_201311 PYCCKИИ ...
Page 156: ...24 26 0006081537_201311 中 文 最小电离电流3μA 如果有需求 电气图 ...
Page 158: ...26 26 0006081537_201311 中 文 ...
Page 159: ......