min - maX air gate reguLation
Example:
Parameters set to minimum operating power
alfa1 = 30°
V1 = 45 hz
Parameters set to maximum operating power
alfa2 = 75°
V2 = 45 hz
Operating parameters with opening angle of the air gate alfa* = 60°:
Voltage value recalculated by the input signal: 6.7 V
V* = 40 hz
The inverter is equipped with an EEPROM that stores the machine
history of the last ten alarms. To access this data it is necessary to
interface the inverter with the PC by connecting them via the serial
port using the appropriate cable, which can be provided by the
manufacturer on request.