ENGLISH
5 / 32
0006081530_201711
Special precautions when using gas.
•
Check that the feed line and the train comply with current law
and regulations.
•
Check that all the gas connections are properly sealed.
• Do not leave the equipment on when it is not in use and always
close the gas cock.
•
If the user is absent for a prolonged period of time, close the
main gas feed tap to the burner.
• If you smell gas:
-
do not operate electrical switches, phones or any other
object that may cause sparks;
-
open immediately doors and windows to create a draught to
clear the air in the room;
- close the gas cocks;
- have professionally qualified personnel correct the fault.
•
Do not obstruct ventilation openings in the room where there is
gas equipment. Otherwise, dangerous situations may arise with
the build up of toxic and explosive mixtures.
RESIDUAL RISKS
• Even though the product was designed in compliance with the
obligatory standards, residual risks may still be present during
correct operation. They are signalled on the burner through
special Pictograms.
CAUTION
Moving mechanical organs.
CAUTION
Materials at high temperature.
CAUTION
Powered electric panel.
ELECTRIC SAFETY WARNINGS
•
Check that the equipment has a suitable ground system, carried
out following safety standards in force.
• Do not use the gas pipes to ground electrical equipment.
•
If in doubt, call for a careful electrical check by a qualified
technician, since the manufacturer will not be liable for any
damage caused by a poor ground connection.
•
Have qualified personnel check that the electric system is
adequate to equipment maximum power consumption indicated
on the plate.
•
Make sure that system cable section is suitable to equipment
power consumption.
•
Adapters, multiple plugs and/or extension cables may not be
used for the equipment’s power supply.
•
For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance
with current safety regulations (condition of overvoltage
category III).
•
For burner electricity supply use double insulation cables only,
with external isolation at least 1 mm thick.
•
Remove the external insulating seal of the supply pipe necessary
for the connection, preventing the cable to touch metal parts.
•
The electrical supply to the burner must have neutral to ground
connection. If the ionisation current has control with neutral not
to ground, it is essential to make a connection between terminal
2 (neutral) and the ground for the RC circuit.
• The use of any electrically fed components entails complying
with certain fundamental rules, including the following:
- do not touch the equipment with parts of the body that are
wet or damp or with damp feet;
- do not pull on electrical cables;
- do not leave the equipment exposed to atmospheric agents
(such as rain or sun etc.) unless there is explicit provision
for this;
- do not allow the equipment to be used by children or
inexpert persons;
- The power supply cable for the equipment must not be
replaced by the user. In case of cable damage, turn the
equipment off. To replace it contact qualified personnel only;
-
If you decide not to use the equipment for a certain period of
time it is advisable to switch off the electrical power supply
to all components in the system that use electricity (pumps,
burner, etc.).
•
Use regulation-compliant flexible cables EN60335-1:
- in case of PVC sheath, at least type H05VV-F;
- in case of rubber sheath, at least type H05RR-F;
- without any sheath at least type FG7 or FROR.
•
The electric equipment works correctly when the relative
humidity does not exceed the 50% at a maximum temperature
of +40° C. Higher relative humidity are allowed at lower
temperatures(e.g. 90 % at 20° C)
•
The electric equipment works correctly at altitudes of up to 1000
m above the see level.
Summary of Contents for TBG 85 ME
Page 2: ......
Page 31: ...ITALIANO 29 32 0006081530_201711 SCHEMI ELETTRICI...
Page 32: ...ITALIANO 30 32 0006081530_201711...
Page 33: ...ITALIANO 31 32 0006081530_201711...
Page 63: ...ENGLISH 29 32 0006081530_201711 WIRING DIAGRAMS...
Page 64: ...ENGLISH 30 32 0006081530_201711...
Page 65: ...ENGLISH 31 32 0006081530_201711...
Page 67: ......