ENGLISH
6 / 30
0006081041_201809
TECHNICAL SPECIFICATIONS
MODEL
TBG 85P
Maximum natural gas heat power
kW
850
Minimum natural gas heat power
kW
170
¹) natural gas emissions
mg/kWh
Class 2
Operation
Two-stage
50 Hz natural gas transformer
26 kV - 40 mA - 230/240 V
60 Hz natural gas transformer
26 kV - 40 mA - 230/240 V
Maximum natural gas heat rate
Stm³/h
90
Minimum natural gas heat rate
Stm³/h
18
Maximum natural gas pressure
hPa (mbar)
360
Minimum natural gas pressure
hPa (mbar)
25
Maximum propane thermal power
kW
850
Minimum propane thermal power
kW
170
Maximum propane thermal flow rate
Stm³/h
35
Minimum propane thermal flow rate
Stm³/h
7
Maximum propane pressure
hPa (mbar)
360
Minimum propane pressure
hPa (mbar)
26
²)propane emissions
mg/kWh
Class 3
50hz fan motor
kW
1.1
60hz fan motor
kW
1.1
Absorbed electrical power* 50hz
kW
1.39
Absorbed electrical power* 60hz
kW
1.39
50 Hz power supply voltage
3N ~ 400V ± 10%
60 Hz power supply voltage
1N ~ 380V ± 10%
Protection rating
IP 44
Flame detection
IONISATION PROBE
Control box
LME 22...
Air flow rate regulation
electric servomotor
Operating ambient air temperature
°C
-15 ÷ +40
Sound pressure**
dBA
76
Sound power***
dBA
88
Weight with packaging
kg
71.63
Weight without packaging
kg
57
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion
chamber.
* Total absorption at start-up with ignition transformer on.
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory
environment conditions and cannot be compared to measurements carried out in different locations.
*** Acoustic pressure was obtained characterizing the manufacturer's laboratory with a sample source; this measurement has a class 2
accuracy (engineering class) with a standard deviation of 1.5 dB(A).
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural
gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh
propane gas
1
≤ 230
2
≤ 180
3
≤ 140
Summary of Contents for TBG 85P