INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE
OPERATION AND THEIR ELIMINATION
IRREGULARITY
The burner does not start.(The
equipment does not perform the
start up program).
Defective flame with sparks.
Flame not properly shaped with
presence of smoke and soot.
Defective flame, flickering or
protruding from combustion
orifice.
POSSIBLE CAUSE
1 Thermostats (boiler or room) or pressure
switches are open.
2 Photoresistor in short circuit.
3 Absence of line voltage, main switch
open, meter switch tripped or absence of
line voltage.
4 Thermostat line not wired according to
diagram or open thermostats.
5 Equipment internal fault.
1 Spraying pressure is too low.
2 Too much combustion air.
3 Nozzle inefficient because dirty or worn.
4 Water in the fuel.
1 Insufficient combustion air flow.
2 Nozzle inefficient because dirty or worn.
3 Nozzle capacity too low with respect to
combustion chamber volume.
4 Combustion chamber unsuitably
designed or too small.
5 Unsuitable refractory coating (it reduces
excessively the space of the flame).
6 Boiler or chimney ducts blocked.
7 Spraying pressure is low.
1 Excessive draught, only when there is an
extractor in the chimney.
2 Nozzle inefficient because dirty or worn.
3 Water in the fuel.
4 Dirty flame disk.
5 Too much combustion air.
6 Air passage between flame disk and
diffuser excessively closed.
REMEDY
1 Raise the thermostats settings, or wait that
the contacts close for natural decrease of
temperature or pressure.
2 Replace it.
3 Activate switches or wait for power to
return.
4 Check the connections and thermostats.
5 Replace it.
1 Restore it at the required value.
2 Reduce combustion air
3 Clean or replace.
4 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
1 Increase combustion air.
2 Clean or replace.
3 Decrease diesel flow rate to suit the
chamber (thermal power will obviously be
lower than necessary) or replace the boiler.
4 Increase nozzle flow by replacing it.
5 Modify it, carefully abiding by the
instructions given by boiler manufacturer.
6 Arrange for cleaning.
7 Restore it at the required value.
1 Adjust the suction fan speed by changing
the pulley diameter.
2 Clean or replace.
3 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
4 Clean.
5 Reduce combustion air.
6 Correct the position of the combustion head
regulating device.
Summary of Contents for TBML 200 MC
Page 2: ......
Page 48: ...ITALIANO 46 54 0006081544_201907 SCHEMI ELETTRICI ...
Page 49: ...ITALIANO 47 54 0006081544_201907 ...
Page 50: ...ITALIANO 48 54 0006081544_201907 ...
Page 52: ...ITALIANO 50 54 0006081544_201907 ...
Page 53: ...ITALIANO 51 54 0006081544_201907 ...
Page 54: ...ITALIANO 52 54 0006081544_201907 ...
Page 56: ...ITALIANO 54 54 0006081544_201907 ...
Page 102: ...ENGLISH 46 54 0006081544_201907 WIRING DIAGRAMS ...
Page 103: ...ENGLISH 47 54 0006081544_201907 ...
Page 104: ...ENGLISH 48 54 0006081544_201907 ...
Page 106: ...ENGLISH 50 54 0006081544_201907 ...
Page 107: ...ENGLISH 51 54 0006081544_201907 ...
Page 108: ...ENGLISH 52 54 0006081544_201907 ...
Page 110: ...ENGLISH 54 54 0006081544_201907 ...
Page 111: ......