FLAME SENSOR
The flame detecting UV photocell must be able to trigger upon system
operation if the flame turns off (this check must be carried out after at
least one minute from the ignition).
The photocell current value required for a correct operation of the equi
-
pment is indicated in the wiring diagram.
Even the slightest greasiness will compromise the passage of rays
through the photocell bulb, thus preventing the sensitive internal ele
-
ment from receiving the quantity of radiation necessary for it to work
properly. If the bulb is fouled with diesel, fuel oil, etc... it must be pro
-
perly cleaned.
CAUTION / WARNINGS
Even simply touching the bulb with fingers may leave a slight
greasiness which could compromise photocell operation.
The UV cell does not detect daylight or the light from a common lamp.
Sensitivity can be checked with a flame (lighter) or with the electric
discharge between the electrodes of a common ignition transformer.
To ensure a proper operation, the UV photocell current value must be
sufficiently stable and not go below the minimum value required for the
equipment.
It may be necessary to tentatively find the best position by sliding (axial
or rotational movement) the casing that contains the photocell with re-
spect to the fastening clamp.
This can be checked by connecting a micro-ammeter, with a suitable
scale, in series to one of the two UV photocell connection cables. Ob
-
viously the + and - polarity must be respected.
The burner should be capable of locking out and remain in that con
-
dition when, during the ignition sequence in the time pre-set by the
control box, the flame does not regularly appear.
The lock-out condition leads to an immediate fuel shut-off, the system
stops and the lock warning light comes on.
To check the photocell and lock-out efficiency, proceed as follows:
1 Start the burner
2 After at least one minute from ignition remove the UV photocell
from its seat, and simulate a flame failure. The burner flame
must turn off, the equipment will immediately shut down in "lock-
out" condition.
3 The equipment can only be reset manually by pressing the reset
button. The shut-down efficiency test must be performed at least
twice.
Check the efficiency of the thermostats or boiler pressure switches
(they should shut down the burner when triggered).
0002960151a
BT 3..
BN
BK
BU
00061
11044
20 / 42
0006160409_202305
ENGLISH
Summary of Contents for TBML 2000 ME
Page 2: ......
Page 38: ...SCHEMI ELETTRICI TBML 1200ME 1600ME 2000ME BT 335 36 42 0006160409_202305 ITALIANO...
Page 39: ...TBML 1200ME 1600ME 2000ME BT 335 37 42 0006160409_202305 ITALIANO...
Page 40: ...TBML 1200ME 1600ME 2000ME BT 335 38 42 0006160409_202305 ITALIANO...
Page 41: ...TBML 1200ME 1600ME 2000ME BT 335 39 42 0006160409_202305 ITALIANO...
Page 42: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 40 42 0006160409_202305 ITALIANO...
Page 44: ...42 42 0006160409_202305 ITALIANO...
Page 80: ...WIRING DIAGRAMS TBML 1200ME 1600ME 2000ME BT 335 36 42 0006160409_202305 ENGLISH...
Page 81: ...TBML 1200ME 1600ME 2000ME BT 335 37 42 0006160409_202305 ENGLISH...
Page 82: ...TBML 1200ME 1600ME 2000ME BT 335 38 42 0006160409_202305 ENGLISH...
Page 83: ...TBML 1200ME 1600ME 2000ME BT 335 39 42 0006160409_202305 ENGLISH...
Page 84: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 40 42 0006160409_202305 ENGLISH...
Page 86: ...42 42 0006160409_202305 ENGLISH...
Page 87: ......