ENGLISH
12 / 44
0006160028_201510
GAS SUPPLY LINE
The basic diagram of the gas supply line is shown in the figure
below.
The gas train is certified in accordance with Standard EN 676 and
is supplied separately from the burner.
DANGER / CAUTION
Install a manual on/off valve upstream of the gas valve ac-
cording to the layout shown in the diagram illustrating the
gas train principle.
GAS BURNER SCHEMATIC DIAGRAM
M
M
12
10
9
14
11
13
8
4
7
6
5
3
2
1
0002910950N2
RESPONSIBILITY OF THE INSTALLER
GAS TRAIN SUPPLIED BY THE MANUFACTURER
1 Manual shut-off valve
2 Vibration-proof joint
3 Gas filter
4 Minimum gas pressure switch
5 Safety valve
6 Pressure regulator.
7 Valve seal control device (mandatory for burners with maximum rated
heating capacity higher than 1200kW)
8 Two-stage operating valve
9 Air regulation servomotor
10 Air regulation shutter
11 Air pressure switch
12 Combustion head
13 Gas throttle valve
14 Gas regulation servomotor
Summary of Contents for TBML 50 ME
Page 2: ......
Page 40: ...SCHEMI ELETTRICI ITALIANO 38 44 0006160028_201510...
Page 41: ...ITALIANO 39 44 0006160028_201510...
Page 42: ...ITALIANO 40 44 0006160028_201510...
Page 43: ...ITALIANO 41 44 0006160028_201510...
Page 44: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 42 44 0006160028_201510...
Page 46: ...ITALIANO 44 44 0006160028_201510...
Page 84: ...ENGLISH 38 44 0006160028_201510 WIRING DIAGRAMS...
Page 85: ...ENGLISH 39 44 0006160028_201510...
Page 86: ...ENGLISH 40 44 0006160028_201510...
Page 87: ...ENGLISH 41 44 0006160028_201510...
Page 88: ...ENGLISH 42 44 0006160028_201510 BT1 BA BP I1 I2 I3 I4...
Page 90: ...ENGLISH 44 44 0006160028_201510...
Page 91: ......