ENGLISH
8 / 44
0006160003_201510
¹) NATURAL GAS EMISSIONS
Classes defined according to Standard EN 676.
Class
NOx emissions in mg/kWh -
natural gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE EMISSIONS
CO emissions, natural gas/propane ≤ 100 mg/kWh
Class
NOx emissions in mg/kWh -
propane gas
1
≤ 230
2
≤ 180
3
≤ 140
³) DIESEL EMISSIONS
Classes defined according to Standard EN 267.
Class
NOx emissions in mg/
kWh - diesel fuel
CO emissions in mg/
kWh - diesel fuel
1
≤ 250
≤ 110
2
≤ 185
≤ 110
3
≤ 120
≤ 60
OPERATING RANGE
TBML 50 ME / MC
10
8
6
4
2
0
100
200
300
400
500
600
kW
0002922890
mbar
IMPORTANT
The working fields are obtained from test boilers corresponding to the
standard EN267 for liquid fuels and EN676 for gas fuels and are in-
dicative for the combination burner-boiler. For correct working of the
burner, the size of the combustion chamber must correspond to current
regulations; if not the manufacturers must be consulted.
The burner should not work outside the indicated work range.
Min thermal power TBML 50 LPG = 120kW