ELECTRICAL CONNECTIONS
•
The power lines must be distanced from the hot parts.
•
The burner can be installed exclusively in environments with
pollution degree 2 as specified in Standard EN 60204-1.
•
Make sure that the power line to which the unit will be connected,
has frequency and voltage values suitable for the burner.
•
The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can
be accessed easily.
•
The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current absorbed
by the burner.
•
For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance
with current safety regulations.
• Refer to the wiring diagram for electrical connections (line and
thermostats).
•
Remove the external insulating seal of the supply pipe necessary
for the connection, preventing the cable to touch metal parts.
To carry out the connection of the burner to the power supply line pro
-
ceed as follows:
•
Remove the cover by unscrewing the screws (1), without remo
-
ving the transparent door. In this way the burner’s electrical panel
can be accessed.
•
Loosen the screws (2) and after removing the cable clamp plate
(3), make the 7 pole plug, the 4 pole plug and the modulation
control cable come through the hole. Connect the power supply
cables (4) to the contactor, secure the ground cable (5) and
tighten the relating cable gland.
•
Reposition the cable clamp plate. Turn the cam (6) so that the
plate exerts sufficient pressure on the cables, then tighten the
screws that fasten the plate. Finally, connect the related plugs and
modulation command cable, if installed.
1
1
0002934780a
14 / 50
0006160331_202310
ENGLISH
Summary of Contents for TBML 80 MC
Page 2: ......
Page 45: ...SCHEMI ELETTRICI TBML 50 MC 200 MC 43 50 0006160331_202310 ITALIANO...
Page 46: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ITALIANO...
Page 47: ...45 50 0006160331_202310 ITALIANO...
Page 49: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ITALIANO...
Page 50: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ITALIANO...
Page 51: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ITALIANO...
Page 95: ...WIRING DIAGRAMS TBML 50 MC 200 MC 43 50 0006160331_202310 ENGLISH...
Page 96: ...TBML 50 MC 200 MC 44 50 0006160331_202310 ENGLISH...
Page 97: ...45 50 0006160331_202310 ENGLISH...
Page 99: ...TBML 260 MC 360 MC 47 50 0006160331_202310 ENGLISH...
Page 100: ...TBML 260 MC 360 MC 48 50 0006160331_202310 ENGLISH...
Page 101: ...TBML 260 MC 360 MC 49 50 0006160331_202310 ENGLISH...
Page 103: ......