After pulling the ignition and ionisation cables (14) out of their
electrodes, unscrew the locking nuts (6) from the mixing unit. Lo-
osen nut (9) and completely unscrew the fastening screw on the
delivery coupling (19).
•
Slightly lower the gas delivery connection (30) and remove the en-
tire mixing unit in the direction indicated by the arrow.
•
Having completed the maintenance work, replace the combustion
head, following in reverse order the operations described above,
after having checked the correct position of ignition and ionisation
electrodes.
DANGER / ATTENTION
When closing the burner, gently pull the two ignition cables
towards the electrical panel, putting them slightly in tension,
then arrange them in their housing on the scroll. This will en-
sure that the two cables do not get damaged by the fan during
burner operation.