3. Setup and Connections
Vlinx MESR9xx Modbus Gateway
Page 20
Manual Documentation Number MESR9xx-4508m
www.bb-elec.com/
www.bb-europe.com/
Reloading Factory Defaults
To reload Factory Defaults,
press and hold the Mode switch for more than 10 seconds.
The LED indicators respond as follows:
1.
The Ready LED blinks three times per second while the button is being pressed.
2.
The Modbus gateway is in Factory Default Mode when:
•
On the MESR901: Port 1 LED and the Ready LED are both On.
•
On MESR902x models: Port 1 LED and the Port 2 LED are both On.
The Modbus gateway reloads all factory default configuration parameters.
3.
The LEDs go back to their normal states when the device resumes normal operation.
Note: Factor default parameters are listed in Appendix A