background image

6

CONFIGURING A FIELDBUS GATEWAY

The  Fieldbus  Gateway  is  configured  using  Fieldbus  Gateway  Manager 

software. Updates to the software for new features and drivers are posted on the 

website as they become available. By configuring the Fieldbus Gateway using 

the latest version of the software, you are assured that your unit has the most up 

to date feature set. The software can configure the Fieldbus Gateway through 

the  RS232/PG  port,  USB/PG  port,  Ethernet,  or  CompactFlash. The  USB/PG 

port is connected using a standard USB cable with a Type B connector.

The driver needed to use the USB port will be installed with the software. 

The RS232/PG port uses a programming cable made by B&B to connect to the 

DB9  COM  port  of  your  computer.  If  making  your  own  cable,  refer  to  the 

“Fieldbus Gateway Port Pin Outs” for wiring information.

The CompactFlash can be used to program a Fieldbus Gateway by placing a 

configuration  file  and  firmware  on  the  CompactFlash  card. The  card  is  then 

inserted into the target Fieldbus Gateway and powered.

CABLES AND DRIVERS

B&B  has  a  wide  range  of  cables  and  drivers  for  use  with  many  different 

communication types. A list of these drivers and cables along with pin outs is 

available from B&B’s website. If making your own cable, refer to the “Fieldbus 

Gateway Port Pin Outs” for wiring information.

USB, DATA TRANSFERS FROM THE 

COMPACTFLASH CARD

In order to transfer data from the CompactFlash card via the USB port, a 

driver  must  be  installed  on  your  computer.  This  driver  is  installed  with  the 

software and is located in the folder C:\Program Files\B&B Electronics\Vlinx 

Fieldbus  Gateway  Manager\Device  after  the  software  is  installed.  This  may 

have  already  been  accomplished  if  your  Fieldbus  Gateway  was  configured 

using the USB port.

Once the driver is installed, connect the Fieldbus Gateway to your PC with a 

USB  cable,  and  follow  “Mounting  the  CompactFlash”  instructions  in  the 

Fieldbus Gateway Manager user manual.

Note: The USB port is for system set-up and diagnostics and is not intended for 

permanent connection.

ETHERNET COMMUNICATIONS

Ethernet  communications  can  be  established  at  either  10  BASE-T  or  100 

BASE-TX.  The  Fieldbus  Gateway’s  RJ45  jack  is  wired  as  a  NIC  (Network 

Interface Card). For example, when wiring to a hub or switch use a straight-

through cable, but when connecting to another NIC use a crossover cable.

The Fieldbus Gateway Manager manual contains additional information on 

Ethernet communications.

RS232 PORTS

The Fieldbus Gateway has two RS232 ports. There is the RS232/PG port and 

the  COMMS  port.  Although  only  one  of  these  ports  can  be  used  for 

programming,  both  ports  can  be  used  for  communications  with  a  PLC.  The 

RS232/PG port can be used for either master or slave protocols.

RS422/485 PORT

The Fieldbus Gateway has one RS422/485 port. This port can be configured 

to act as either RS422 or RS485.

Note: All B&B devices connect A to A and B to B.

DH485 COMMUNICATIONS

The Fieldbus Gateway’s RS422/485 COMMS port can also be used for Allen 

Bradley DH485 communications.

WARNING

: DO NOT use a standard DH485 cable to connect this port to Allen 

Bradley equipment. A cable and wiring diagram are available from B&B.

TX

5V

8

1

7

2

TxB

TxA

130K

130K

5

TxEN (OC)

RX

130K

5V

130K

RxB

4

RxA

3

GND

6

TxEN (OC)

TX/RX

130K

5

TxA

2

8

130K

5V

7

1

TxB

6

GND

RS422/485 4-WIRE 

CONNECTIONS

RS485 2-WIRE 

CONNECTIONS

COMMUNICATING WITH THE Fieldbus Gateway

WARNING - DO NOT CONNECT OR DISCONNECT CABLES 

WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE 

NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND 

DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT 

CONNECTION.

Summary of Contents for VLINX VFG1000

Page 1: ...ce which can be purchased as part of a kit that includes a manual and cables or downloaded free of charge SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the...

Page 2: ...use only Installation Category II Pollution Degree 2 8 POWER CONNECTION Removable wire clamp screw terminal block Wire Gage Capacity 24 AWG to 12 AWG Torque 4 45 to 5 34 in lb 0 5 to 0 6 N m 9 MOUNTI...

Page 3: ...ession devices is effective The following EMI suppression devices or equivalent are recommended Ferrite Suppression Cores for signal and control cables Fair Rite part number 0443167251 TDK part number...

Page 4: ...485 USB PG RS232 PG ETHERNET CF STS CHASSIS GND OR REM SLC 5 03 CPU RUN BATT FLT RUN RS232 DH485 FORCE PROG VDC PWR OUT 24 PWR OUT COM VAC NEUT 120 240 VAC USER POWER POWER RS232 PG USB PG RS232 PG ET...

Page 5: ...the available cables WARNING Do NOT use a standard DH 485 cable to connect this port to Allen Bradley equipment PORT 3 ETHERNET CONNECTION RS232 RS485 5 EXPANSION 24VDC 10 USB PG TxA PIN 8 GREEN YELL...

Page 6: ...lished if your Fieldbus Gateway was configured using the USB port Once the driver is installed connect the Fieldbus Gateway to your PC with a USB cable and follow Mounting the CompactFlash instruction...

Page 7: ...ft operating systems will not lock the drive unless they need to write data Windows 98 may lock the drive any time it is mounted thereby interfering with logging Refer to Mounting the CompactFlash in...

Page 8: ...l Headquarters 707 Dayton Road P O Box 1040 Ottawa IL 61350 Phone 815 433 5100 Fax 815 433 5104 B B Electronics Ltd European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland Phone 353...

Reviews: