Electrical Installation
14
Manual Documentation Number: ZXTx-IO-x-0712m
Figure 3-2
Mounting Ear dimensions
3.5
Cabling Options
The Zlinx Xtreme module has two holes
of 0.875” diameter for cable installation. Cable gland or conduit mounting is possible.
A cable gland and conduit hub are included as accessories. Unused hole must be plugged by the supplied membrane gland in
order to maintain IP67 rating.
3.5.1 Cable Glands
NOTE: the Cable Glands cannot be used for Class 1 Division 2 applications. Please see the Quick Start
Guide for UL Class 1 Division 2 installation instructions.
A Cable Gland is used to maintain the water tight rating while allowing a cable to enter the enclosure. The assembly consists
of black molded nylon body, hex nut, cable nut and a rubber gasket and cable seal.
Figure 3-3
IP67 Cable Gland