1TT –TIMER + TERMOREGOLATORE - Reference Manual  - Pag. 5 di 7 

parameters

 

 

Description

 

 

                      Values

 

 

Default

 

 

Note

 

SP 

(*)

 

Setpoint  

- 99 :: [ Maximum Setpoint]       

20°C 

 

                           Disposable 

 Parameters with the “123” password only

 

AL

 

Alarm 

[min] :: [max] 

100°C 

 

Int 

              Kind of probe 

tcJ 

Termocouple J 

tcH 

Termocouple K 

tcb 

Termocouple B 

tce 

Termocouple E 

tcn 

Termocouple N 

tcr 

Termocouple R 

tcs 

Termocouple S 

tct 

Termocouple T 

pt1 

Pt100 

p10 

Pt1000 

 

TC J 

 

Act 

Working method 

Hot 

Heating

 

Col 

Raffreddamento

 

 

Hot 

Setting 

COL

 the 

controller  will work by 
ON/OFF method w.algor. 

Eco 

 ECO mod 

0 (off) :: 999 

0°C 

 

BSC 

Gradient of ramp 

0 :: 1 

The setpoint can 
automatically change 

nSP 

Min. setpoint 

- 99 :: 999 

- 30 °C 

 

mSP 

Max. setopoint 

- 99 :: 999  

400°C 

 

Tc 

Time of Cycle 

0,1 :: 999 

15 s 

 

PB 

Proportional Band 

0 (regolazione ON-OFF) : 100 

2 % 

Percentage of the range 

Ti 

Integral Time 

0 :: 999 

120 s 

Integral Time 

td 

            Derivative Time 

- 1 :: 999 

30 s 

Select -1 to work 
automatically in  Ti/4 

OFS 

           TemperatureOffset 

- 100 :: +100 

0 °C 

 

HSO 

Positive differential off SET 

0 :: 999 

0 °C 

Used in case of  ON-OFF 
reg. 

HSU 

Negative differential off SET 

0 :: 999 

1 °C 

Used in case of ON-OFF 

 

ALM 

 

Relay Alarm Mode 

 
Absolute Band Alarm    

   Relay

 - ( 

1 off / 2 on 

Finestra o deviazione       

Relay

 - ( 

4 off / 3 on 

 

 

 

ALS 

            Setpoint Alarm 

0 :: 1 

Solo per allarme  relè 
finestra o deviazione 

ALH 

Absolute High Alarm .  

 0 :: 999 

600 °C

   