1TT –TIMER + TERMOREGOLATORE - Reference Manual  - Pag. 6 di 7 

 

 TUNe MODE  – ACCESS WITHOUT PASSWORD  

 
Press for 5 second  the  

  button, the upper display will show 

SET

 and the lower 

t1

;  press the  

▲  button 

and the  

lower display will show 

timE

; press again  

 and the lower display will show 

dev

; press the  

 button and the upper  

display will show 

tun

,  the lower 

no 

;  

Press the  

 button and the lower display will show the following tune options : 

no

   =     Disabled. 

Man

 =   Manual SET UP Output. 

OnE

  =   At first turning ON. 

All

 

 

   

=   At every turning ON. 

 
After inserting the the tune mode, the confirmation that the programming has been successfully completed will be 
shown by the flashing  

9  9

  on the display.  

 
 
 
 
 
 
 

 
 
 
 
 
 
 

ALL 

Absolute Low Alarm. 

  0 :: 999 

0 °C 

 

MPe 

Pulse generator in case of 
error of probe 
(percentualizzatore) 

0 :: 1 

In caso di errore sonda 
lo strumento passa alla 

modalità 

percentualizzatore

 

MAN 

Manual setup 

Percent generator 

0 :: 1 

Se impostato, lo 
strumento funziona 
come un 

percentualizzatore

 

OUT 

Percent manual value) 

0 :: 100 

50 % 

La percentuale è 
calcolata sul parametro 
TMS (tempo di ciclo in 
modalità 
percentualizzatore) 

LSP 

Display functions 

0 :: 1 

Se impostato limita la 
visualizzazione della 

temperatura al setpoint 