Model No Heat Strip
Motor HP / Load Amp
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-01
1/3hp / 2.6
3.25
15
Model BDAH-02
1/3hp / 2.6
3.25
15
Model BDAH-03
1/2hp / 4.6
5.75
15
Model BDAH-04
1/2hp / 4.6
5.75
15
Model BDAH-05
1hp / 7
8.75
15
11
Scranton, IA 51462
Phone (712) 652-3424
www.bdmfginc.com
ELECTRICAL DATA INFORMATION SHEET
All Models without Emergency Backup Heat
Model BDAH-02
5kw Emergency Heat Strip
Model BDAH-01
3kw Emergency Heat Strip
Model BDAH-03
10kw Emergency Heat Strip
Model BDAH-04
10kw or 15kw Emergency Heat Strip
Model BDAH-05
10kw or 15kw Emergency Heat
Model With Heat Strip
KW / Load
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-01
3KW / 12.5
15.63
20
Model With Heat Strip
KW / Load
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-02
5KW / 20.8
26
30
Model With Heat Strip
KW / Load
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-03
10KW / 41.7
52.125
60
Model With Heat Strip
KW / Load
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-04
10KW / 41.7
52.125
60
Model BDAH-04
15KW / 62.5
78.125
80
Model With Heat Strip
KW / Load
MCA
(Minimum Circuit Ampacity)
MOP
(Maximum Overcurrent Protection)
Model BDAH-05
10KW / 41.7
52.125
60
Model BDAH-05
15KW / 62.5
78.125
80