22
Scranton, IA 51462
Phone (712) 652-3424
www.bdmfginc.com
Model BDAH-01
Heating Data
CFM
P.D.
(Ft. H2O)
GPM
105°F Entering Water
110°F Entering Water
115°F Entering Water
70°F Entering Air
70°F Entering Air
70°F Entering Air
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Heating
Capacities b
ased
up
on
0%
Gl
ycol
300
2.4
2
9.1
95.8
10.4
99.5
11.8
103.1
8.5
4
10
100
11.4
104.2
12.9
108.5
350
2.4
2
9.8
94.9
11.4
98.4
12.9
102
8.5
4
11.2
99.4
12.8
103.5
14.4
107.7
400
2.4
2
10.7
94.2
12.3
97.6
13.9
101
8.5
4
12.2
98.8
14
102.9
15.8
107
500
2.4
2
12
92.9
13.8
96.1
15.5
99.3
8.5
4
14
97.9
16.1
101.9
18.1
105.8
Heating
Cap
acities
b
ased
up
on
10
% Gly
col
300
2.5
2
8.9
96
10.2
99.6
11.5
103.3
8.9
4
9.9
100
11.3
104.3
12.7
108.5
350
2.5
2
9.7
95.2
11.1
98.7
12.6
102.2
8.9
4
10.9
99.4
12.6
103.6
14.2
107.8
400
2.5
2
10.4
94.4
11.9
97.9
13.5
101.3
9
4
12
98.9
13.7
103
15.5
107.1
500
2.5
2
11.5
93.3
13.3
96.5
15
99.7
9
4
13.7
98
15.7
102
17.7
106
Heating
Cap
acities
b
ased
up
on
20
% Gly
col
300
2.6
2
8.5
96.2
9.8
99.9
11.1
103.6
9.4
4
9.7
100
11.1
104.3
12.5
108.6
350
2.6
2
9.3
95.5
10.7
99
12.1
102.6
9.4
4
10.8
99.5
12.4
103.6
13.9
107.8
400
2.6
2
9.9
94.8
11.4
98.3
12.9
101.7
9.4
4
11.7
99
13.5
103.1
15.2
107.2
500
2.6
2
10.9
93.8
12.6
97
14.2
100.3
9.4
4
13.4
98.1
15.3
102.1
17.3
106.1
Electric Heat Strip Information
PART#
DESCRIPTION
AH3KWHEAT
3KW ELECTRIC STRIP HEAT
Electric Heat Strip Capacities
KW
BTU/H
TOTAL AMPS
240V
208V
240V
208V
240V
208V
3KW
2.25KW 10236 BTU/H 7677 BTU/H 12.5 AMPS 10.81 AMPS
NOTE:
The above listed heat strip part numbers and heat strip capacities data is only for the HSS
®
Air Handlers. These
are specially designed for the electrical heat strip units for
B&D Mfg., Inc.
The electrical heat strip units are factory
installed if ordered with electrical heat strip and can be field installed also if ordered without electrical heat strip.