26
Scranton, IA 51462
Phone (712) 652-3424
www.bdmfginc.com
Model BDAH-03
Heating Data
CFM
P.D.
(Ft. H2O)
GPM
105°F Entering Water
110°F Entering Water
115°F Entering Water
70°F Entering Air
70°F Entering Air
70°F Entering Air
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Total MB/H
Exit H2O°F
Heating
Capacities b
ased
up
on
0%
Gl
ycol
1000
2.1
4
29.2
90.3
33.4
93.1
37.7
96
7.7
8
33.3
96.6
38.1
100.4
43
104.1
1100
2.1
4
30.6
89.6
35.1
92.3
39.5
95
7.7
8
35.6
96
40.8
99.7
47
103.4
1200
2.1
4
31.9
88.9
36.6
91.5
41.2
94.2
7.7
8
37.8
95.5
43.2
99.1
48.7
102.7
1350
2.1
4
33.6
88.1
38.5
90.5
43.4
93
7.7
8
40.7
95
46.5
98.3
52.4
101.7
Heating
Cap
acities
b
ased
up
on
10
% Gly
col
1000
2.3
4
27.9
90.8
32.1
93.7
36.4
96.5
8.1
8
32.8
96.7
37.5
100.5
42.3
104.2
1100
2.3
4
29.2
90.1
33.6
92.9
38.1
95.6
8.1
8
35
96.1
40.1
99.8
45.2
103.5
1200
2.3
4
30.4
89.6
35
92.2
39.6
94.8
8.1
8
37
95.6
42.4
99.2
47.8
102.8
1350
2.3
4
31.8
75.8
36.7
91.4
41.6
93.8
8.1
8
39.8
94.9
45.5
98.5
51.3
101.9
Heating
Cap
acities
b
ased
up
on
20
% Gly
col
1000
2.4
4
26.2
91.5
30.2
94.4
34.3
97.3
8.5
8
32
96.8
36.7
100.5
41.5
104.3
1100
2.4
4
27.4
90.9
31.5
93.7
35.8
96.5
8.5
8
34
96.2
39.1
99.9
44.2
103.6
1200
2.4
4
28.3
90.4
32.7
93.1
37.1
95.9
8.5
8
35.9
95.8
41.3
99.4
46.7
103
1350
2.4
4
29.6
89.7
34.1
92.3
38.8
95.8
8.5
8
38.4
95.6
44.2
98.6
51
102.1
Electric Heat Strip Information
PART#
DESCRIPTION
AH10KWHEAT
10KW ELECTRIC STRIP HEAT
Electric Heat Strip Capacities
KW
BTU/H
TOTAL AMPS
240V
208V
240V
208V
240V
208V
10KW
7.51KW 34100 BTU/H 25609 BTU/H 41.7 AMPS 36.1 AMPS
NOTE:
The above listed heat strip part numbers and heat strip capacities data is only for the HSS
®
Air Handlers. These
are specially designed for the electrical heat strip units for
B&D Mfg., Inc.
The electrical heat strip units are factory
installed if ordered with electrical heat strip and can be field installed also if ordered without electrical heat strip.