X20 system modules • Digital output modules • X20DO4633
X20 system User's Manual 3.10
1177
Product ID
X20DO4633
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB32 terminal block separately
Order 1x X20BM32 bus module separately
Spacing
25
+0.2
mm
Table 376: X20DO4633 - Technical data
1)
Number of outputs x residual voltage (on-state voltage) x nominal output current (A calculation example can be found on the B&R website in the download
area for the module.)
4.15.15.4 Status LEDs
For a description of the various operating modes, see the 2.11.1 "re LEDs" section.
Figure
LED
Color
Status
Description
Off
Module supply not connected
Single flash
RESET mode
Blinking
PREOPERATIONAL mode
On
RUN mode
r
Green
Flickering (ap-
prox. 10 Hz)
Module is in OSP state
Off
Module supply not connected or everything OK
On
Error or reset status
e
Red
Single flash
Loss of zero-crossing signal (I/O supply voltage not applied or too low)
e + r
Red on / Green single flash
Invalid firmware
1 - 4
Orange
Control status of the corresponding digital output
4.15.15.5 Pinout
The following points must be taken into consideration when wiring the module:
•
For thermal reasons, wires with a cross-section ≥1.5 mm² must be used to wire the module.
•
The neutral return lines for the outputs must be wired to the terminal block separately for each channel
and must not be bypassed in the field.
•
A line filter must be used for the 240 V supply that provides ≥40 dB attenuation at 150 kHz and works
up to 5 MHz.
DO 1
DO 2
N
N
N
N
X
20
D
O
4
63
3
r
e
1 2
L
L
N
N
3 4
DO 3
DO 4