X20 system modules • Digital output modules • X20DO6325
1218
X20 system User's Manual 3.10
4.15.19.11.5.3 Short circuit to voltage
Name:
StatusInput02
DigitalStatusVcc01 to DigitalStatusVcc06
In this register, a short circuit can be indicated by setting the corresponding channel bit.
Function model 0 - Standard only:
The "packed outputs" setting in the AS I/O configuration is used to determine whether all of this registers' bits should
be set up individually as data points in the AS I/O mapping ("DigitalStatusVcc01" through "DigitalStatusVcc06") or
whether this register should be displayed as an individual USINT data point ("StatusInput02").
Data type
Value
Information
0 to 63
Packed outputs = on
USINT
See bit structure
Packed outputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
No error
0
DigitalStatusVcc01
1
Channel 1: Short circuit to voltage
...
...
0
No error
5
DigitalStatusVcc06
1
Channel 6: Short circuit to voltage
6 - 7
Reserved
0
4.15.19.11.5.4 Open line
Name:
StatusInput03
DigitalStatusBw01 to DigitalStatusBw06
In this register, an open line can be indicated by setting the corresponding channel bit.
Function model 0 - Standard only:
The "packed outputs" setting in the AS I/O configuration is used to determine whether all of this registers' bits should
be set up individually as data points in the AS I/O mapping ("DigitalStatusBw01" through "DigitalStatusBw06") or
whether this register should be displayed as an individual USINT data point ("StatusInput03").
Data type
Value
Information
0 to 63
Packed outputs = on
USINT
See bit structure
Packed outputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
No error
0
DigitalStatusBw01
1
Channel 1: Open line
...
...
0
No error
5
DigitalStatusBw06
1
Channel 6: Open line
6 - 7
Reserved
0