X20 system modules • Digital output modules • X20DO8332
1278
X20 system User's Manual 3.10
4.15.26.10.4 Digital outputs
The output status is transferred to the output channels with a fixed offset (<60 µs) in relation to the network cycle
(SyncOut).
4.15.26.10.4.1 Switching state of digital outputs 1 to 8
Name:
DigitalOutput
DigitalOutput01 to DigitalOutput08
The switching state of digital outputs 1 to 8 are stored in this register.
Function model 0 - Standard only:
The "packed outputs" setting in the AS I/O configuration is used to determine whether all of this registers' bits
should be set up individually as data points in the AS I/O mapping ("DigitalOutput01" through "DigitalOutput0x") or
whether this register should be displayed as an individual USINT data point ("DigitalOutput").
Data type
Value
Information
0 to 255
Packed outputs = on
USINT
See bit structure
Packed outputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
Digital output 01 reset
0
DigitalOutput01
1
Digital output 01 set
...
...
0
Digital output 08 reset
7
DigitalOutput08
1
Digital output 08 set
4.15.26.10.5 Reading the module ID
Name:
asy_ModulID
This register offers another possibility for reading the module ID.
Data type
Value
UINT
Module ID