X20 system modules • Digital output modules • X20DO9322
1290
X20 system User's Manual 3.10
Product ID
X20DO9322
R
DS(on)
210 mΩ
Max. continuous current
6.0 A
Peak short circuit current
<12 A
Switching on after overload or short circuit cutoff
Ca. 10 ms (depends on the module temperature)
Switching delay
2)
0 -> 1
<300 µs
1 -> 0
<300 µs
Switching frequency
Resistive load
2)
Max. 500 Hz
Inductive load
See section "Switching inductive loads"
Braking voltage when switching off inductive loads
Typ. 50 VDC
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 414: X20DO9322 - Technical data
1)
Number of outputs x R
DS(on)
x nominal output current
2
2)
@ ≤ 1 kΩ
Summary of Contents for X20 System