X20 system modules • Digital output modules • X20DOD322
X20 system User's Manual 3.10
1299
4.15.29.4 Status LEDs
Figure
LED
Color
Status
Description
Off
Module supply not connected
Single flash
Reset mode
Blinking
PREOPERATIONAL mode
Green
On
RUN mode
Off
Module supply not connected or everything OK
Red
Single flash
Warning/Error on an I/O channel. Level monitoring for digital outputs has been
triggered.
S
Red on / Green single flash
Invalid firmware
1 - 8
Orange
Output status of the corresponding digital output
Table 418: Status LEDs
4.15.29.5 Pinout
DO 1
DO 3
DO 5
DO 2
DO 4
DO 6
DO 7
GND
GND
DO 8
GND
GND
GND
GND
GND
GND
1
3
5
7
2
4
6
8
X
20
D
O
D
32
2
S
Figure 407: Pinout
4.15.29.6 Connection example
GND
+24 VDC
GND
+24 VDC
DO
Actuator 5
Actuator 7
Actuator 3
Actuator 6
Actuator 8
Actuator 4
Actuator 2
Actuator 1
Figure 408: Connection example
Caution!
If the module is operated outside of specifications, the output current can increase above the maximum
permissible nominal current. This applies to individual channels and also to the summation current
for the module.
Therefore sufficient cable cross sections or external safety measures must be used.
Summary of Contents for X20 System
Page 2: ......