X20 system modules • X20 electronics module communication • X20CS1020
1534
X20 system User's Manual 3.10
4.18.5.3 Technical data
Product ID
X20CS1020
Short description
Communication module
1x RS232
General information
B&R ID code
0x1FCF
Status indicators
Data transfer, operating status, module status
Diagnostics
Module run/error
Yes, using status LED and software
Data transfer
Yes, using status LED
Power consumption
Bus
0.01 W
Internal I/O
1.44 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
IF1 - Bus
Yes
IF1 - I/O supply
No
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Interfaces
IF1 interface
Signal
RS232
Design
Connection made using 12-pin X20TB12 terminal block
Max. distance
900 m
Transfer rate
Max. 115.2 kbit/s
FIFO
1 kB
Handshake lines
RTS, CTS
Controller
UART type 16C550 compatible
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 465: X20CS1020 - Technical data