X20 system modules • Expandable bus controllers • X20BC1083
1712
X20 system User's Manual 3.10
4.19.2.8 Slot for interface modules
Depending on the bus base, up to two interface modules can be installed on the left side of the expandable bus
controller:
Bus base
Slots for interface modules
X20BB81
1
X20BB82
2
Table 500: Slots for interface modules for various bus bases
4.19.2.9 Operating netX modules with the X20BC1083 bus controller
The following must be taken into account to operate netX modules with the bus controller without problems:
•
A minimum revision ≥E0 is required for the bus controller.
•
NetX modules can only be operated with POWERLINK V2. V1 is not permitted.
4.19.2.10 SG3
This module is not supported on SG3 targets.
4.19.2.11 SG4
This module comes with preinstalled firmware. The firmware is also part of the Automation Runtime operating
system for the PLC. If the two versions are different, the Automation Runtime firmware is loaded to the module.
The latest firmware is made available automatically when updating Automation Runtime.