X20 system modules • X20 interface module communication • X20IF1086-2
X20 system User's Manual 3.10
1825
4.23.16.3 Technical data
Product ID
X20IF1086-2
Short description
Communication module
1x POWERLINK (V1/V2) managing or controlled node
General information
B&R ID code
0xB455
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
Power consumption
1.8 W (Rev. <D0: 2.0 W)
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - X1
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
Fieldbus
POWERLINK (V1/V2) managing or controlled node
Type
Type 4
1)
Standard (compliance)
ANSI/IEEE 802.3
Design
1x duplex LC
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-FX
Half-duplex
Yes
Full-duplex
No
Autonegotiation
No
Auto-MDI / MDIX
No
Controller
POWERLINK MAC
Wave length
1300 nm
Cable fiber type
Multimode fiber with 62.5/125 μm or 50/125 μm core diameter
LC connector on both sides
Cable length
Ethernet TCP/IP
Max. 400 m between two stations (segment length)
POWERLINK
Max. 2 km between two stations (segment length)
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Slot
In X20 CPU
Table 610: X20IF1086-2 - Technical data
1)
See the POWERLINK help system under "General information, Hardware - IF/LS".
Summary of Contents for X20 System
Page 2: ......