X20 system modules • X20 interface module communication • X20IF2181-2
X20 system User's Manual 3.10
1863
Green - Status
Description
Triple flash (approx. 1 Hz)
Mode
The module is in the READY_TO_OPERATE state.
Managing node (MN)
Cyclic and asynchronous communication. The received PDO data is ignored.
Controlled node (CN)
The module configuration is complete. Normal cyclic and asynchronous communication. The PDO data sent corresponds
to the PDO mapping. Cyclic data is not yet evaluated, however.
An LED lit red in this mode indicates a failure of the MN.
On
Mode
The module is in PRE_OPERATIONAL_2 mode. PDO mapping is active and cyclic data is being evaluated.
Blinking (approx. 2.5 Hz)
Mode
The module is in STOPPED mode.
Managing node (MN)
This status is not possible for the MN.
Controlled node (CN)
No output data is produced or input data supplied. It is only possible to enter or leave this mode after the MN has given
the appropriate command.
Table 651: Status/Error LED as Status LED - POWERLINK operating mode
200
200
1000
200
200
200
200
1000
200
200
All times in ms
Flickering
Blinking
Single flash
Triple flash
200
200
200
1000
Double flash
Figure 592: LED status indicators - Blinking patterns
4.23.25.4.2 System failure error codes
Incorrect configuration or defective hardware can cause a system failure error.
The error code is indicated by the red error LED using four switch-on phases. The switch-on phases have a duration
of either 150 ms or 600 ms. Error code output is repeated cyclically after 2 seconds.
Error description
Error code indicated by red status LED
RAM error:
The module is defective and must be replaced.
●
●
●
-
Pause
●
●
●
-
Pause
Hardware error:
The module or a system component is defective and must be replaced.
-
●
●
-
Pause
-
●
●
-
Pause
Table 652: Status/Error ("S/E") LED - System stop error codes
Key:
●
... 150 ms
-
... 600 ms
Pause ... 2 sec. delay
Summary of Contents for X20 System
Page 2: ......