X20 system modules • X20 interface module communication • X20IF2181-2
1864
X20 system User's Manual 3.10
4.23.25.5 Operating and connection elements
LED status indicators
Station number switches
POWERLINK connection with
2x RJ45 ports for easy wiring
Figure 593: Operating and connection elements
4.23.25.6 POWERLINK station number
The station number for the POWERLINK station is set using the two number switches. The station number can
also be directly configured using Automation Studio.
4.23.25.6.1 POWERLINK V2
Switch position
Description
0x00
Reserved, switch position not permitted.
0x01 - 0xEF
Node number of POWERLINK station. Operation as controlled node.
0xF0
Operation as managing node.
0xF1 - 0xF7
Reserved, switch position not permitted.
0xF8
CPU redundancy: Function as primary CPU
0xF9
CPU redundancy: Function as secondary CPU
0xFA - 0xFF
Reserved, switch position not permitted.
Table 653: POWERLINK V2 - Node numbers
4.23.25.6.2 Ethernet mode
In this mode, the interface is operated as an Ethernet interface. The INA2000 station number can be set using the
B&R Automation Studio software.
4.23.25.7 RJ45 ports
Information about cabling X20 modules with an Ethernet interface can be found in the module's download section
RJ45 port 2 (X2)
RJ45 port 1 (X1)