4.25.3.3 Technical data
Product ID
X20MM3332
Short description
I/O module
3 full-bridge outputs
General information
B&R ID code
0xA982
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Output
Yes, using status LED and software
I/O supply
Yes, using status LED and software
Power consumption
Bus
0.01 W
Internal I/O
0.8 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
External I/O supply bus
Yes
Channel - Bus
Yes
Channel - Channel
No
Certification
CE
Yes
cULus
Yes
KC
Yes
GOST-R
Yes
Motor bridge - Power unit
Quantity
3
Execution
H bridge
Type
Full bridge
High-side driver
Low-side driver
Nominal voltage
24 VDC
Switching voltage
24 VDC (-15% / +20%)
Nominal current
3.0 A
Maximum current
5.0 A (250 ms)
Total nominal current
10.0 A
Current value measurement
Resolution
100 mA
Data collection
In the driver
Output protection
Thermal cutoff for overcurrent and short circuit
Supply voltage
No reverse polarity protection
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
0 to 50°C
Vertical installation
Not permitted
Derating
See section "Derating"
Storage
-25 to 70°C
Transport
-25 to 70°C
Relative humidity
Operation
5 to 95%
Storage
5 to 95%
Transport
5 to 95%
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 696: X20MM3332 - Technical data