4.26.2 X20CM4810
4.26.2.1 Order data
Model number
Short description
Figure
Other functions
X20CM4810
X20 analog input module for vibration measurement and
analyse of condition monitoring exercises. 4 IEPE analog input
51,5625 kHz sampling frequency 24 bit converter resolution
Required accessories
Bus modules
X20BM31
X20 bus module for double-width modules, 24 VDC keyed, in-
ternal I/O supply continuous
Terminal blocks
X20TB12
X20 terminal block, 12-pin, 24 VDC keyed
Optional accessories
Cables
0ACC0020.01-1
Cable for acceleration sensor, length 2 m, 2x 0.34 mm², M12
socket on sensor side, can be used in cable drag chains, UL
listed
0ACC0050.01-1
Cable for acceleration sensor, length 5 m, 2x 0.34 mm², M12
socket on sensor side, can be used in cable drag chains, UL
listed
0ACC0100.01-1
Cable for acceleration sensor, length 10 m, 2x 0.34 mm², M12
socket on sensor side, can be used in cable drag chains, UL
listed
0ACC0150.01-1
Cable for acceleration sensor, length 15 m 2x 0.34 mm², Female
M12 connector on sensor side, cable, UL listed
0ACC0200.01-1
Cable for acceleration sensor, length 20 m, 2x 0.34 mm², M12
socket on sensor side, can be used in cable drag chains, UL
listed
Sensors
0ACS100A.00-1
Acceleration sensor, nominal sensitivity 100 mV/g, top exit
0ACS100A.90-1
Acceleration sensor, nominal sensitivity 100 mV/g, side exit
Table 720: X20CM4810 - Order data
4.26.2.2 Technical data
Information:
The X20CM4810 module is only supported by Automation Studio 3.0.90.x and Automation Runtime
versions >= J3.09, J4.01 and O4.02.
4.26.2.2.1 Technical data
Product ID
X20CM4810
Short description
I/O module
X20 4-channel analog input module for vibration measurement and analysis of condition monitoring tasks
General information
Isolation voltage between channel and bus
500 V
eff
Nominal voltage
24 VDC ±20%
B&R ID code
0xC8F9
Status indicators
Run, error, vibration inputs 1 to 4
Diagnostics
Module run/error
Yes, using status LED and software
Power consumption
Bus
0.01 W
Internal I/O
2.5 W
Electrical isolation
Channel - Bus
Yes
Channel - Channel
No
Certification
CE
Yes
cULus
Yes
GOST-R
Yes
Analog inputs
Quantity
4
Input type
IEPE sensor: Acceleration
Digital converter resolution
24-bit
Table 721: X20CM4810 - Technical data