X20 system modules • Other functions • X20CM4810
2208
X20 system User's Manual 3.10
4.26.2.8.2 Sensor cables
4.26.2.8.2.1 Order data
Model number
Length
Short description
0ACC0020.01-1
2 m
0ACC0050.01-1
5 m
0ACC0100.01-1
10 m
0ACC0150.01-1
15 m
0ACC0200.01-1
20 m
Cable for acceleration sensor,
2x 0.34 mm
2
, 1x 0.25 mm
2
,
female M12 connector on sensor,
1x 25 mm² shield connection,
can be used in cable drag chains, UL/CSA listed
4.26.2.8.2.2 Technical data
Name
0ACC0xx0.01-1
General information
Number of poles
3
Cable length
x
Characteristic values of the wire
Cable type
PUR halogen-free black shielded
AWG signal lead
22
Conductor design signal lead
42x 0.10 mm
Wire diameter incl. insulation
1.27 mm ±0.02 mm
Wall thickness insulation
≥0.21 mm (wire insulation)
Approx. 1.1 mm (outer sheath)
Cable external diameter
5.9 mm ±0.15 mm
Insulation resistance
≥100 GΩ*km (at 20°C)
Conductor resistance
Max. 58 Ω/km (at 20°C)
Shielding
Braided copper wires
Cable weight
44 kg/km
Smallest flex radius, fixed
29.5 mm
Smallest flex radius, movable
59 mm
Number of flex cycles
4,000,000
Flex radius
59 mm
Movement range
10 m
Movement speed
3 m/s
Acceleration
10 m/s²
Ambient temperature (during operation)
-40°C ... 80°C (cable, inflexible installation)
-25°C ... 80°C (cable, flexible installation)
EN 60529 protection
IP67
4.26.2.8.2.3 Sensor cables with M12 connector
1
2
4
3
5
2
Pos.
Pieces
Name
Note
1
1
Sensor cable
2x 0.34 mm² (1501702 3x 0.34)
2
1
M12 socket (axial)
M12 socket (M12x1 A coded)
3
2
Wire end ferrules (2x sensor cables)
3203066 AI 0.34-8 TQ
4
1
Heat shrink tubing
5
1
Shield connection
1x 0.25 mm² black
6
1
Wire end ferrules (1x shield connection)
3200632 AI 0.25-12 BU
Summary of Contents for X20 System
Page 2: ......