Product ID
X20AT2222
Temperature measurement monitoring
Range exceeded (neg.)
0x8001
Above upper range limit
0x7FFF
Open line
0x7FFF
General error
0x8000
Open inputs
0x7FFF
Resistance measurement monitoring
Above upper range limit
0xFFFF
Open line
0xFFFF
General error
0xFFFF
Open inputs
0xFFFF
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 835: X20AT2222 - Technical data