X20 system modules • Temperature modules • X20ATA312
2410
X20 system User's Manual 3.10
Product ID
X20ATA312
Isolation voltage between channel and bus
500 V
eff
Linearization method
Internal
Measuring current
1 mA
Temperature sensor standardization
-200 to 850°C
Reference
1568 Ω ±0.1%
Temperature measurement range
-200 to 850°C
Permitted input signal
Short-term max. 28.8 V
Max. error at 25°C
1)
Gain
0.0059%
2)
Offset
0.0015%
3)
Max. gain drift
<0.00065% per °C
2)
Max. offset drift
<0.000025% per °C
3)
Non-linearity
<0.001%
3)
Standardized value range for resistance measure-
ment
19 to 390.0 Ω
Temperature measurement monitoring
Range exceeded (neg.)
0x80000001
Above upper range limit
0x7FFFFFFF
Open line
0x7FFFFFFF
General error
0x80000000
Open inputs
0x7FFFFFFF
Resistance measurement monitoring
Range exceeded (neg.)
0x80000001
Above upper range limit
0xFFFFFFFF
Open line
0xFFFFFFFF
General error
0x80000000
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 or X20TB1F terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 839: X20ATA312 - Technical data
1)
To ensure accuracy, modules with a power loss <1.2 W must be inserted to the left and right of this module.
2)
Based on the current resistance value.
3)
Based on the entire resistance measurement range.
Summary of Contents for X20 System
Page 2: ......