X20 system modules • Temperature modules • X20ATA492
X20 system User's Manual 3.10
2421
Product ID
X20ATA492
Measurement range
Sensor temperature
Type J: Fe-CuNi
-210 to 1200°C
Type K: NiCr-Ni
-270 to 1372°C
Type N: NiCrSi-NiSi
-270 to 1298°C
Type S: PtRh10-Pt
-50 to 1768°C
Type B: PtRh30-PtRh6
0 to 1820°C
Type R: PtRh13-Pt
-50 to 1760°C
Type E: NiCr-CuNi
-270 to 997°C
Type C: WRe5-WRe26
0 to 2310°C
Type T: Cu-CuNi
-270 to 400°C
Terminal temperature
-40 to 130°C
Voltage
±65.534 mV
Sensor standard
EN 60584
Resolution
Sensor temperature
1 LSB = 0.1 °C
Terminal temperature
1 LSB = 0.1 °C
Voltage
Depending on gain, 1 LSB = 1 µV or 2 µV
Normalization
Type J
-210.0 to 1200.0°C
Type K
-270.0 to 1372.0°C
Type N
-270.0 to 1298.0°C
Type S
-50.0 to 1768.0°C
Type B
0.0 to 1820.0°C
Type R
-50.0 to 1760.0°C
Type E
-270.0 to 997.0°C
Type C
0.0 to 2310.0°C
Type T
-270.0 to 400.0°C
Terminal temperature (PT1000)
-40.0 to 130.0°C
Voltage
Depending on gain ±32.767 mV or ±65.534 mV
Monitoring
Range exceeded (neg.)
0x8001
Above upper range limit
0x7FFF
Open line
0x7FFF
Open inputs
0x7FFF
General error
0x8000
Conversion procedure
Sigma Delta
Linearization method
Internal
Permitted input signal
Max. ±5 V
Input filter
1st-order low pass / cut-off frequency 500 Hz
Basic accuracy
Type J
±0.10% at 25°C
2)
Type K
±0.11% at 25°C
2)
Type N
±0.11% at 25°C
2)
Type S
±0.17% at 25°C
2)
Type B
±0.19% at 25°C
2)
Type R
±0.15% at 25°C
2)
Type E
±0.10% at 25°C
2)
Type C
±0.12% at 25°C
2)
Type T
±0.15% at 25°C
2)
Voltage
±0.03% at 25°C
3)
Maximum gain drift
Channel
0.01 %/°C
4)
Terminal temperature (PT1000)
0.003 %/°C
4)
Max. offset drift
Type J
0.0019 %/°C
3)
Type K
0.0025 %/°C
3)
Type N
0.0030 %/°C
3)
Type S
0.0081 %/°C
3)
Type B
0.0111 %/°C
3)
Type R
0.0072 %/°C
3)
Type E
0.0017 %/°C
3)
Type C
0.0039 %/°C
3)
Type T
0.0072 %/°C
3)
Terminal temperature (PT1000)
0.0050 %/°C
3)
Voltage
0.001 %/°C
3)
Terminal temperature compensation
Operating modes
Internal/remote or external
Basic accuracy at 25°C without taking the
PT1000 sensor into consideration
±0.06%
Accuracy of the internal terminal temperature
With natural convection
±15°C after 20 min
With artificial convection
±30°C after 20 min