X20 system modules • Temperature modules • X20ATA492
X20 system User's Manual 3.10
2431
4.31.6.9.4 Variable mapping in Automation Studio (CANIO)
Read
Write
Name
Data type
Cyclic
Acyclic
Cyclic
Acyclic
Variables – Channel 01
Temperature01
INT
●
INT
SampleTime01
DINT
●
SINT
IOCycleCount01
INT
●
CompensationValue01
INT
●
ExternalCompensationTemperature01
INT
●
StatusInput01
USINT
●
Underflow01
BOOL
●
Overflow01
BOOL
●
OpenLine01
BOOL
●
CompTemperaturError01
BOOL
●
ConversionError01
BOOL
●
SumError01
BOOL
●
ParameterError01
BOOL
●
IoSuppError01
BOOL
●
CompensationStatus01
USINT
●
CompUnderflow01
BOOL
●
CompOverflow01
BOOL
●
CompOpenLine01
BOOL
●
CompConversionError01
BOOL
●
CompSumError01
BOOL
●
CompParameterError01
BOOL
●
CompIoSuppError01
BOOL
●
Variables – Channel 02
Temperature02
INT
●
INT
SampleTime02
DINT
●
SINT
IOCycleCount02
INT
●
CompensationValue02
INT
●
ExternalCompensationTemperature02
INT
●
StatusInput02
USINT
●
Underflow02
BOOL
●
Overflow02
BOOL
●
OpenLine02
BOOL
●
CompTemperaturError02
BOOL
●
ConversionError02
BOOL
●
SumError02
BOOL
●
ParameterError02
BOOL
●
IoSuppError02
BOOL
●
CompensationStatus02
USINT
●
CompUnderflow02
BOOL
●
CompOverflow02
BOOL
●
CompOpenLine02
BOOL
●
CompConversionError02
BOOL
●
CompSumError02
BOOL
●
CompParameterError02
BOOL
●
CompIoSuppError02
BOOL
●
Table 848: Variable mapping in Automation Studio (CANIO)