X20 system modules • Temperature modules • X20ATC402
X20 system User's Manual 3.10
2467
4.31.8.9.7 Temperature measurement - Configuration
The temperature measurement channels can be configured independently of each other. All the registers required
for each channel are arranged separately.
The "SensorType" register needs to be adjusted in order to enable a temperature channel. The rest of the registers
complement this configuration and only need to be defined as required.
4.31.8.9.7.1 SensorType
Designations (pChannelName):
Cfo_SensorType01
Cfo_SensorType[02...06]
The "SensorType" registers control the basic functionality of a temperature channel.
Data type
Values
UINT
See bit structure
Bit structure:
Bit
Product ID
Note
0…5
Standardization
Sensor type used
6…7
Reserved
-
8…11
Method of compensation
Reference point
12
Reserved
-
0
Replace with static preset value
13
Replacement value
1
Retain last valid value
0
Valid value range for sensor type
14
Additional user limits
1
Additional restrictions to value range
0
Channel not converted by the ADC
15
Temperature channel (on/off)
1
Channel registered on the ADC
Sensor type:
00…000000 - Sensor J (Fe-CuNi)
01…000001 - Sensor K (NiCr-Ni)
02…000010 - Sensor N (NiCrSi-NiSi)
03…000011 - Sensor S (PtRh10-Pt)
04…000100 - Sensor R (PtRh13-Pt)
05…000101 - Sensor C (WRe5-WRe26)
06…000110 - Sensor T (Cu-CuNi)
07…000111 - Sensor B (PtRh30-PtRh6)
08…001000 - Sensor E (NiCr-CuNi)
Reference point:
0…0000 - Compensation A
1…0001 - Compensation B
4…0100 - Temperature model implemented for special terminal
8…1000 - External compensation
Raw values without linearization and temperature compensation
61…111101 - RawValue1; Resolution 1.0625 µV; Measurement range ±35 mV
62…111110 - RawValue2; Resolution 2.125 µV; Measurement range ±70 mV
Summary of Contents for X20 System