Coated modules • Analog input modules • X20cAI4632-1
2500
X20 system User's Manual 3.10
Product ID
X20cAI4632-1
Nonlinearity
Voltage
<0.01%
4)
Current
<0.015%
5)
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20cBM11 bus module separately
Spacing
12.5
+0.2
mm
Table 909: X20cAI4632-1 - Technical data
1)
To reduce power dissipation, B&R recommends bridging unused inputs on the terminals or configuring them as current signals.
2)
Ta min.: 0°C
Ta max.: See environmental conditions
3)
Based on the current measured value.
4)
Based on the 22 V measurement range.
5)
Based on the 22 mA measurement range.