Coated modules • Bus controllers • X20cBC0088
X20 system User's Manual 3.10
2521
5.5.4.3 Technical data
Product ID
X20cBC0088
Short description
Bus controller
EtherNet/IP Adapter (slave)
General information
B&R ID code
0xE67F
Status indicators
Module status, network status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
Network status
Yes, using status LED and software
Power consumption
Bus
2.0 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Fieldbus - X2X Link
Yes
Fieldbus - I/O
Yes
Certification
CE
Yes
ATEX Zone 2
1)
Yes
GOST-R
Yes
Interfaces
Fieldbus
EtherNet/IP Adapter (slave)
Design
2x shielded RJ45 port (switch)
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
10/100 Mbit/s
Transmission
Physical interfaces
10 BASE-T/100 BASE-TX
Half-duplex
Yes
Full-duplex
Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Min. cycle time
2)
Fieldbus
1 ms
X2X Link
500 μs
Synchronization between bus systems possible
No
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20cPS9400 or X20cPS9402 power supply module separately
Order 1x X20cBB80 bus base separately
Spacing
3)
37.5
+0.2
mm
Table 927: X20cBC0088 - Technical data
1)
Ta min.: 0°C
Ta max.: See environmental conditions
2)
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
3)
The spacing refers to the width of the X20cBB80 bus base. An X20cPS9400 or X20cPS9402 power supply module is always required for the bus controller.