Coated modules • Digital output modules • X20cDO6321
2576
X20 system User's Manual 3.10
Product ID
X20cDO6321
Diagnostic status
Output monitoring with 10 ms delay
Leakage current when switched off
75 µA
R
DS(on)
120 mΩ
Peak short circuit current
<7 A
Switching on after overload or short circuit cutoff
Ca. 10 ms (depends on the module temperature)
Switching delay
0 -> 1
<300 µs
1 -> 0
<300 µs
Switching frequency
Resistive load
Max. 500 Hz
Braking voltage when switching off inductive loads
Typ. 50 VDC
Isolation voltage between channel and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20cBM11 bus module separately
Spacing
12.5
+0.2
mm
Table 971: X20cDO6321 - Technical data
1)
Number of outputs x R
DS(on)
x Nominal output current
2
(A calculation example can be found on the B&R website in the download area for the module.)