Coated modules • Digital output modules • X20cDO6639
2578
X20 system User's Manual 3.10
Product ID
X20cDO6639
Actuator supply
External
Contact resistance
15 mΩ at 6 VDC / 1A
Switching delay
0 -> 1
≤10 ms
1 -> 0
≤10 ms
Isolation voltage
Contact - Contact
Tested at 750 VAC
Contact - Coil
Tested at 2300 VAC
Service life
Electrical
2)
Min. 120 x 10
3
ops. (at 2 A / 240 VAC)
Mechanical
Min. 2 x 10
7
ops
Switching capacity
Minimum
0.05 W DC / 2.4 W AC
Maximum
60 W DC / 480 W AC
Total power of all channels
AC
3000 W
DC
360 W
Protective circuit
Internal
None
External
AC
RC combination or VDR
DC
Inverse diode, RC combination or VDR
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB32 terminal block separately,
Order 1x X20cBM12 bus module separately
Spacing
12.5
+0.2
mm
Table 973: X20cDO6639 - Technical data
1)
Number of outputs x Contact resistance x Nominal output current
2
(A calculation example can be found on the B&R website in the download area for the
module.)
2)
With a resistive load. See also section "Electrical service life"