Coated modules • X20 interface module communication • X20cIF10E3-1
2622
X20 system User's Manual 3.10
5.20.7.3 Technical data
Product ID
X20cIF10E3-1
Brief description
Communication module
PROFINET RT device (slave)
General information
B&R ID code
0xE238
Status indicators
Module status, network status, data transfer
Diagnostics
Module status
Yes, using status LED and software
Network status
Yes, using status LED and software
Data transfer
Yes, using status LED
Power consumption
2.0 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - IF1
Yes
PLC - IF2
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
GOST-R
Yes
Interfaces
Fieldbus
PROFINET RT device (slave)
Design
2x shielded RJ45 port (switch)
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Controller
netX100
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Slot
In the X20c CPU and in the X20cBC1083 expandable bus controller
Table 1009: X20cIF10E3-1 - Technical data