X20 system modules • Analog input modules • X20AP31x1
X20 system User's Manual 3.10
351
4.3.14.10.13.4 Warning threshold for the calculated neutral current
Name:
INWarnTh0
Current value for monitoring the calculated neutral line current.
Data type
Value
Information
UINT
0 to 65000
Resolution 0.001 A
4.3.14.10.13.5 Warning threshold for the measured neutral current.
Name:
INWarnTh1
Current value for monitoring the measured neutral line current.
Data type
Value
Information
UINT
0 to 65000
Resolution 0.001 A
4.3.14.10.13.6 Warning threshold for exceeding voltage THD
Name:
THDNUTh
Percentage value defining warning threshold for THD ratio.
Data type
Value
Information
UINT
0 to 10000
Resolution 0.01%
4.3.14.10.13.7 Warning threshold for exceeding current THD
Name:
THDNITh
Percentage value defining warning threshold for THD ratio.
Data type
Value
Information
UINT
0 to 10000
Resolution 0.01%