X20 system modules • Bus receivers and Bus transmitters • X20BT9100
608
X20 system User's Manual 3.10
4.8.3.3 Technical data
Product ID
X20BT9100
Short description
Bus transmitter
X2X Link bus transmitter with supply for I/O
General information
B&R ID code
0x1BC2
Status indicators
X2X bus function, operating status, module status
Diagnostics
Module run/error
Yes, using status LED and software
X2X bus function
Yes, using status LED
Power consumption
1)
Bus
0.5 W
Internal I/O
As bus transmitter
0.1 W
Additionally as supply module
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Input I/O supply
Input voltage
24 VDC -15% / +20%
Fuse
Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection
No
Output I/O supply
Rated output voltage
24 VDC
Behavior if a short circuit occurs
Required line fuse
Permitted contact load
10.0 A
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB06 or X20TB12 terminal block separately
Order 1x X20BM11 or X20BM15 bus module separately
Spacing
12.5
+0.2
mm
Table 202: X20BT9100 - Technical data
1)
The specified values are maximum values. The exact calculation is also available for download as a data sheet with the other module documentation on
the B&R website.
Summary of Contents for X20 System