X20 system modules • Compact CPUs System modules • X20PS9500
X20 system User's Manual 3.10
635
4.10.4.3 Technical data
Product ID
X20PS9500
Brief description
Power supply module
24 VDC supply module for compact or fieldbus CPU, X2X Link supply and I/O
Interfaces
1x RS232, 1x CAN bus
1)
General information
B&R ID code
0x2018
Status indicators
Overload, operating state, module status, RS232, CAN bus
1)
Diagnostics
Module run/error
Yes, using status LED and software
CAN bus data transfer
1)
Yes, using status LED
RS232 data transfer
Yes, using status LED
Overload
Yes, using status LED and software
Power consumption
2)
Bus
1.42 W
Internal I/O
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
CPU/X2X Link feed - CPU/X2X Link supply
Yes
I/O feed - I/O supply
No
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
CPU / X2X Link supply input
Input voltage
24 VDC -15% / +20%
Input current
Max. 0.7 A
Fuse
Integrated, cannot be replaced
Reverse polarity protection
Yes
CPU / X2X Link supply output
Nominal output power
7.0 W
Parallel operation
Yes
3)
Redundant operation
Yes
Overload behavior
Short circuit / temporary overload protection
Input I/O supply
Input voltage
24 VDC -15% / +20%
Fuse
Required line fuse: Max. 10 A, slow-blow
Reverse polarity protection
No
Output I/O supply
Rated output voltage
24 VDC
Behavior if a short circuit occurs
Required line fuse
Permitted contact load
10.0 A
Interfaces
IF1 interface
Signal
RS232
Design
Connection made using 12-pin X20TB12 terminal block
Transfer rate
Max. 115.2 kbit/s
IF3 interface
1)
Signal
CAN bus
Design
Connection made using 12-pin X20TB12 terminal block
Transfer rate
Max. 1 Mbit/s
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Table 218: X20PS9500 - Technical data