X20 system modules • Counter modules • X20DC1196
690
X20 system User's Manual 3.10
4.11.5.8.3.3 Homing with reference enable input
Regardless of the referencing mode, it is possible using this register to prevent the home position from being
applied when the corresponding reference input voltage level occurs (see 4.11.5.8.4.2 "Input state of digital inputs
1 to 2": bit 4). The desired setting can be configured by a one-off acyclic write.
Voltage level for reference enable activation
Name:
ConfigOutput26
The voltage level of the digital inputs to activate reference enable is configured with this register.
Data type
Value
Filter
0x00
Reference enable is active at 0 VDC
0x10
Reference enable for digital input 1 is active at 24 VDC
0x20
Reference enable for digital input 2 is active at 24 VDC
USINT
0x30
Reference enable for both digital inputs is active at 24 VDC
Reference enable of the input
Name:
ConfigOutput27
This register can be used to define whether the reference enable is activated.
Data type
Value
Filter
0x00
Reference enable input OFF (default)
0x10
Reference enable input 1 enabled
0x20
Reference enable input 2 enabled
USINT
0x30
Reference enable input 1 and 2 enabled