X20 system modules • Counter modules • X20DC1396
748
X20 system User's Manual 3.10
Product ID
X20DC1396
Isolation voltage between home enable switch and
bus
500 V
eff
Switching threshold
Low
<5 VDC
High
>15 VDC
ABR incremental encoder
Encoder inputs
24 V, asymmetrical
Counter size
16/32-bit
Input frequency
Max. 100 kHz
Evaluation
4x
Encoder supply
Module-internal, max. 600 mA
Input filter
Hardware
≥2 µs
Software
-
Input current at 24 VDC
Approx. 1.3 mA
Input resistance
18.4 kΩ
Switching threshold
Low
<5 VDC
High
>15 VDC
Overload behavior of the encoder supply
Short circuit protection, overload protection
Isolation voltage between encoder and bus
500 V
eff
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 240: X20DC1396 - Technical data
Summary of Contents for X20 System