X20 system modules • Counter modules • X20DC2190
X20 system User's Manual 3.10
791
4.11.13.7.14.3 Max. plausible magnet speed
Name:
ConfigOutput13 to ConfigOutput14
ConfigOutput21 to ConfigOutput22
These registers are used to assign the max. plausible magnet speed.
•
Max. speed - magnet 1: ConfigOutput13
•
Max. speed - magnet 2: ConfigOutput14
•
Max. speed - magnet 3: ConfigOutput21
•
Max. speed - magnet 4: ConfigOutput22
Data type
Value
UDINT
0 to 4,294,967,296: Resolution 0.1 mm/s
4.11.13.7.15 Dead time for rods 1 and 2
Name:
ConfigOutput23 to ConfigOutput24
These registers are used to configure the dead time of the respective rod.
•
Dead time for rod 1: ConfigOutput23
•
Dead time for rod 2: ConfigOutput24
To prevent the multiple pulses that occur with some encoders from affecting the measurement, all pulses received
within a configurable timespan from the beginning of the measurement are not evaluated. The range for the dead
time lies between 0 and 255 µs. The following figure illustrates the effects of defining a dead time:
Init pulse
to the encoder
Init pulse
Start/Stop
pulses
from the encoder
Start pulse
Possible
occurring
multiple pulses
1st stop pulse
2nd stop pulse
Pulse
ignored
Measurement time of first counter
Measurement time of second counter
t
t
Figure 287: Pulse Ignored after Start Pulse
Data type
Value
USINT
0 to 255: Resolution 1 µs (default: 0 µs)
4.11.13.7.16 Read configuration register
Name:
ConfigOutput01Read to ConfigOutput04Read
ConfigOutput07Read to ConfigOutput24Read
These registers are used to read the states of the corresponding configuration registers.
4.11.13.7.17 Status register
Name:
StatusInput09 to StatusInput36
These registers are used to store the data read after a parameter upload from transducer rods with DPI/IP protocol
or EP protocol. The registers "StatusInput19" to "StatusInput36" remain empty (0x0000) on transducer rods with
EP protocol.